UPS TYPE PRO 802 S

Rp 15.277.200 (Baru)

Form Factor : Tower
Daya Keluar : 3000VA / 2400W
Voltase Masuk Voltage Range :
Low Line Transfer : 160VAC 5% or 80VAC 5% @ 100% Load, 110VAC 5% or 50VAC 5% @ 50% Load
Low Line Comeback : 175VAC 5% or 85VAC 5% @ 50% Load
High Line Transfer : 300VAC 5% or 150VAC 5%
High Line Comeback : 290VAC 5% or 145VAC 5%
Frequency Range : 40-70Hz (Auto Sensing)
Voltase Keluar : 208/220/230/240VAC or 110/115/120/127VAC
Frequency Range :
Synchronized Range : 47-53Hz or 57-63Hz
Battery Mode : 50Hz 0.25Hz or 60Hz 0.3Hz
Current Crest Ratio : 3:1
Harmonic Distortion :
Linear Load : 4% THD
Non-Linear Load : 7% THD
Transfer Time :
AC Mode to Battery Mode : Zero
Inverter to Bypass : 4ms (Typical)
Waveform (Battery Mode) : Pure Sinewave
Baterai Standard Model :
Battery Type : 12V9AH
Numbers : 6
Typical Recharge Time : 9 hours recover to 90% capacity
Charging Current (max.) : 1A
Charging Voltage : 82.1VDC 1%
Long-Run Model :
Battery Type : Depending on applications
Numbers : 6
Charging Current (max.) : 8A
Charging Voltage : 82.1VDC 1%
Indicators :
LCD Panel : UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge Timer, Fault Conditions
Alarm :
Battery Model : Sounding every 4 seconds
Low Battery : Sounding every seconds
Overload : Sounding twice every seconds
Fault : Continuously sounding
Dimensi Standard Model : 421 x 190 x 318 mm (DxWxH)
Long-Run Model : 421 x 190 x 318 mm (DxWxH)
Berat Standard Model : 28 kg
Long-Run Model : 13 kg

-->